ShinaSystem

Products

Equipment/freezer/air-conditioner controller

Home Products Equipment/freezer/air-conditioner controller XIM-Series
XIM-Series
XIM-Series
Outline

0XIM (eXtension I/O Module) series product is a point extension module of SiBAS-5000/2000 system and is used to extend the input/output quantity of FCU series products (FCU-2000, FCU-2000M, etc.).
0There are 9 different modules depending on input/output types, and maximum 8 modules can be extended for FCU series products and used for monitoring and control the same as the basic points embedded in the FCU.

Functions and features
  • Communication
    • It is connected to FCU through communication to extend the input/output points of the FCU.
    • Communication: RS-485, 1 port, 9,600 bps
    • Communication protocol: XM-Net
  • Setup
    • Communication address setup : DIP switch
    • AI: Individual setup is done using a jumper (hardware setup) in accordance with the input form (voltage, current, or resistance) of each channel.
      The sensor type is set (software setup) in the AI-Type Menu of FCU-2000.
    • AO : Individual setup jumper (hardware setup) in accordance with the input form (voltage, or current) of each channel
  • Power
    • AC 24V, 50Hz/60Hz

Input/output quantity of each model
Model Name Product Name AI AO BI BO PI
XIM-AI16A Analog input module 16
XIM-AO16A Analog output module 16
XIM-BI16A Digital input module 16
XIM-BO16A Digital output module 16
XIM-BIO8A Digital input/
output module
8 8
XIM-ABI8A Analogy digital input module 8 8
XIM-ABI8A Analog input/
output module
8 8
XIM-ABIO4 Analog digital input/
output module
4 4 4 4
XIM-PI16A Pulse input module 16