ShinaSystem

Products

Equipment/freezer/air-conditioner controller

Home Products Equipment/freezer/air-conditioner controller VCM-100A
VCM-100A
VCM - 100 Series
CPU ㆍ32-bit RISC CPU, 72MHz
Memory ㆍFlash Memory : 256 K-Byte
ㆍSRAM : 64 K-Byte
ㆍSheath Flash Memory : 2 M-Byte
Communication function COM 1 ㆍCommunication with high level system
ㆍRS-485 : 9,600 ~ 76,800 BPS
ㆍProtocol : CU-NET, Modbus RTU, BACnet MS/TP(Option)
COM 2 ㆍCommunication with indoor temperature sensor module
ㆍRS-485 : 9,600 BPS
ㆍProtocol : XM-NET
Air volume sensor ㆍWind speed : 0 ~ 15 m/sec (Pressure differential : 0 ~ 125Pa, Operation temperature range : 0 ~ 50 ℃)
ㆍPrecision : ± 3 %
Motor control output ㆍDO : 1, 2 : Floating Output(trIAC)
ㆍAO : 2 ~ 10V DC : (Option)
Analog output ㆍ2 Port, 2 ~ 10V DC, (Max 20mA)
Analog input ㆍPort #1 : NTC 10K or 4 ~ 20mA(Option)
ㆍPort #2 : NTC 10K or 4 ~ 20mA(Option)
ㆍPort #3 : Rtd : PT1000Ω
Digital output ㆍRelay * 3, FAN, For control of heating coil
ㆍQuantity : 3EA, AC 220V, 1A
Digital input ㆍFor status input
ㆍQuantity : 4EA, Dry Contact,
DIP switch setup SW 1 ㆍ1 ~ 5 : For address setup (1 ~ 32)
SW 2 ㆍ1 ~ 2 : For communication mode setup
ㆍ3 ~ 4 : For communication speed setup
Power used ㆍAC 24V, 50/60 Hz. Max 5W
Operation environment ㆍTemperature : -10 ~ 55 ℃
ㆍHumidity : 10 ~ 90 % (Non-Condensing)
Installation method ㆍMounting Hole
Size ㆍ232 x 120 x 70 (W x D x H, mm)