 Products
		
			Products
		
		
			 Equipment/freezer/air-conditioner controller
			Equipment/freezer/air-conditioner controller
		
		
			 VCM-100A
			VCM-100A
		
	| VCM - 100 Series | ||
|---|---|---|
| CPU | ㆍ32-bit RISC CPU, 72MHz | |
| Memory | ㆍFlash Memory : 256 K-Byte ㆍSRAM : 64 K-Byte ㆍSheath Flash Memory : 2 M-Byte | |
| Communication function | COM 1 | ㆍCommunication with high level system ㆍRS-485 : 9,600 ~ 76,800 BPS ㆍProtocol : CU-NET, Modbus RTU, BACnet MS/TP(Option) | 
| COM 2 | ㆍCommunication with indoor temperature sensor module ㆍRS-485 : 9,600 BPS ㆍProtocol : XM-NET | |
| Air volume sensor | ㆍWind speed : 0 ~ 15 m/sec (Pressure differential : 0 ~ 125Pa, Operation temperature range : 0 ~ 50 ℃) ㆍPrecision : ± 3 % | |
| Motor control output | ㆍDO : 1, 2 : Floating Output(trIAC) ㆍAO : 2 ~ 10V DC : (Option) | |
| Analog output | ㆍ2 Port, 2 ~ 10V DC, (Max 20mA) | |
| Analog input | ㆍPort #1 : NTC 10K or 4 ~ 20mA(Option) ㆍPort #2 : NTC 10K or 4 ~ 20mA(Option) ㆍPort #3 : Rtd : PT1000Ω | |
| Digital output | ㆍRelay * 3, FAN, For control of heating coil ㆍQuantity : 3EA, AC 220V, 1A | |
| Digital input | ㆍFor status input ㆍQuantity : 4EA, Dry Contact, | |
| DIP switch setup | SW 1 | ㆍ1 ~ 5 : For address setup (1 ~ 32) | 
| SW 2 | ㆍ1 ~ 2 : For communication mode setup ㆍ3 ~ 4 : For communication speed setup | |
| Power used | ㆍAC 24V, 50/60 Hz. Max 5W | |
| Operation environment | ㆍTemperature : -10 ~ 55 ℃ ㆍHumidity : 10 ~ 90 % (Non-Condensing) | |
| Installation method | ㆍMounting Hole | |
| Size | ㆍ232 x 120 x 70 (W x D x H, mm) | |